Euroka Distributed Power Unit 2KW 57VDC 85-300VAC
Non-Trade customers are welcome to purchase.
For Trade customers, please Sign In or Register for a Trade Account
You are submitting an enquiry for
Euroka Distributed Power Unit represents a next-generation power solution tailored for compact sites. It offers support for both pole-mounted and wall-mounted installations, making it versatile. The DPU finds extensive utility across macro sites, small cells, and remote RRUs.
Features:
Simple Deployment
- Fast installation, 1 hour by 2 people (including power and backup battery)
- Multiple input modes: AC/HVDC
Easy O&M
- Fan-free design, routine maintenance-free
Reliable Power Supply
- Can be used together with lithium-ion battery for energy backup, IP65, working temperature -40℃ to +55℃"
Scenarios:
- RRU/AAU remote site
- Easy Macro Site
- Lamp Site
- Enterprise telecom scenario
Product Type |
CBE-DPU2KW |
System |
|
Dimension (W × D × H) |
60 mm × 300 mm × 400 mm |
Weight |
≤7.5 kg |
Installation Mode |
Wall-mounted, pole-mounted, tower installation |
Rated Power |
2000 W |
Parallel Number |
4 |
Cabling Mode |
Bottom inlet and outlet |
Protection level |
IP65 |
Working Temperature |
−40℃ to +55℃ (without solar radiation) |
Cooling Mode |
Natural heat dissipation |
Operating Environment |
Class C* |
Grid Environment |
1st/2nd/3rd rate grid* |
Environmental |
|
Storage Temperature |
-40oC to +70oC |
Operating Humidity |
5% - 95% (non-condensing) |
Altitude |
-60 to 4000 m (From 2000~4000m, each 200m increases in altitude will decrease the working temperature by 1℃ |
Power Input |
|
Power Input Mode |
220 V AC single-phase |
Input Voltage |
AC: 85 -300 V AC |
Input Frequency |
45 Hz-65 Hz |
AC Input |
1x 16A |
AC SPD |
20 kA/20 kA, 8/20 µs |
Load Output |
|
Output Power |
2000W |
Output Voltage |
-54.5V DC (default), adaptable to 57V DC |
DC Output |
3×40 A Quick plug terminals with replaceable fuse |
Battery Branch |
1x40 A Quick plug terminals |
DC SPD |
10 kA/20 kA, 8/20 µ |
Efficiency |
Maximum efficiency ≥ 95% |
Communication Interface |
South (DB9): 2 × CAN |